Contemporary-control-systems BAScontrol20 User Manual Manual do Utilizador Página 13

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 53
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 12
TD100700-0MB
13
3.2 Cabling Considerations
Function
Signalling and
Data Rate
Minimum Required Cable
Maximum Segment Distance
Ethernet
10BASE-T
10 Mbps
Category 3 UTP
100 m (328 ft)
Ethernet
100BASE-TX
100 Mbps
Category 5 UTP
100 m (328 ft)
I/O
Unspecified
Solid: 1622 AWG
Stranded: 1618 AWG
Unspecified
Table 1 Cabling Considerations
* If using shielded cable, connect to chassis at only one point.
NOTE: Wire size may be dictated by electrical codes for the area where the
equipment is being installed. Consult local regulations.
Observe in Table 1 that 10BASE-T segments can successfully use Category 3, 4 or
5 cable but 100BASE-TX segments must use Category 5 cable. Category 5e
cable is highly recommended as the minimum for new installations.
The Ethernet port of the BASC20 employs Auto-MDIX technology so that either
straight-through or crossover cables can be used to connect to the network.
Vista de página 12
1 2 ... 8 9 10 11 12 13 14 15 16 17 18 ... 52 53

Comentários a estes Manuais

Sem comentários