Contemporary-control-systems BAScontrol20 User Manual Manual do Utilizador Página 35

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 53
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 34
TD100700-0MB
35
5.2.3 Universal Input Configured as Pulse Input
(Channels UI1UI4)
Any channel UI1UI4 can be a Pulse Input for pulse trains in the range of 040 Hz.
You can accept a pulse input with any channel UI1UI8 as follows:
On the Main Page (Figure 13), click a title link from among UI1UI8.
Under BAS Channel Configuration in the new page that appears (Figure 21),
set the Channel Type to Pulse Input. Additional fields then appear …
In the Maximum Value field, set the desired limit for the accumulated pulse
count. It defaults to the absolute maximum of 16,777,215. To reset this
value, simply write a new value in this field. You can also reset this value via
BACnet by taking the channel out of service, writing a desired value such
as 0 and then putting the channel back in service to resume counting.
Set the Pull Up Resistor parameter to Enabled, if used with a passive device.
Note: The BAS Channel Type is Pulse Input, but the BACnet Object Type is
Analog Input. This is because the BACnet object is an accumulator.
Figure 21 Universal Input Configured as Pulse Input
Vista de página 34
1 2 ... 30 31 32 33 34 35 36 37 38 39 40 ... 52 53

Comentários a estes Manuais

Sem comentários