6.3.2 Analog Voltage Output Configuring
You can set any channel 1–6 as type OUTPUT: 010V Analogas shown in Figure 25, using
Channel 1 as an example. Such a channel can supply an output voltage in the range of 010 V.
The channel BACnet type will be Analog Output. On this screen, you can adjust any of the
following parameters.
Channel Name You can rename the channel using no more than 63 characters.
This will be the object name for this channel (followed by the
channel number). For example, Analog Output-1”.
BACnet Unit Group The Electrical default can be set to any option in the list.
BACnet Unit Value The VOLTS default can be set to any option in the list. The available
options depend on the BACnet Unit Group you specify.
BACnet COV Increment Once the channel value changes by this amount (up or down), a
COV message is sent to subscribers.
BACnet Description You can enter any string using no more than 63 characters.
ACTUAL HIGH This specifies the highest value within the range.
ACTUAL LOW This specifies the lowest value within the range.
SCALED HIGH You can set a physical value corresponding to the high value.
SCALED LOW You can set a physical value corresponding to the low value.
Initial Value (Scaled) The Off default outputs 0, but you can preset a Scaled value.
Figure 25 Analog Output Configuration