TD040300-0MF
63
7.4.1.2 Read Channel Data Registers
Two 16-bit registers are assigned to each of the eight channels for reading input data.
Adding an extra register was done to accommodate accumulator values when
measuring pulse inputs. The least significant word resides at the register base address
while the most significant word resides one register location above the base address.
The base register address for channel 1 is 40101 so its most significant word is at
40102. Similarly, channel 8’s base address is at 40115 so its most significant word is at 40116.
0–5000 mV on 0–5 V scale*
0–10000 mV on 0–10 V scale*
0–2000 hundredths of mA on current
–350 to 1110 tenths of °F (2’s comp.)
–370 to 440 tenths of °C (2’s comp.)
Contact off (relay de-energized)
Contact on (relay energized)
* Resolution on 0–5 V scale is 5 mV, and on the 0–10 V scale 10 mV.
Table 4 — Read Channel Data Registers Least Significant Word
Table 5 — Read Channel Data Registers Accumulator
7.4.1.3 Write Channel Data Registers
Unlike input data registers, output data registers only require one register per channel.
Output channel 1 is located at register location 40201 and output channel 8 is located at
register location 40208. Since channel 8 is a relay output, outputting a 0x0001 to
register 40208 will energize the relay coil.
0–2000 tenths of mA on current
De-energize channel 7 relay
De-energize channel 8 relay
Table 6 — Write Channel Data Registers