7.2.2 Analog Input
7.2.3 Analog Output
7.2.4 Analog Value
Property Identifier
Property Datatype
Code
Remarks
Object_Identifier
BACnetObjectIdentifier
R
Object_Name
CharacterString
R
Object_Type
BACnetObjectType
R
Present_Value
REAL
W
Status_Flags
BACnetStatusFlags
R
Status flags will display the status of the channel fault = false
for normal conditions. Overridden = false if the channel is not
forced.
Event_State
BACnetEventState
R
Always normal. Check status flags for real condition.
Out_Of_Service
BOOLEAN
R/W
Units
BACnetEngineeringUnits
R
Priority Array
BACnetPriorityArray
R
Relinquish_Default
REAL
R
COV_Increment
REAL
R
* After the channel is configured as a Pulse Input, its object type will be Analog Value.
Property Identifier
Property Datatype
Code
Remarks
Object_Identifier
BACnetObjectIdentifier
R
Object_Name
CharacterString
R
Object_Type
BACnetObjectType
R
Present_Value
REAL
R
Status_Flags
BACnetStatusFlags
R
Status flags will display the status of the channel fault =
false for normal conditions. Overridden = false if the
channel is not forced. If the channel is a thermistor input
and the thermistor is disconnected, the fault flag will be true.
Event_State
BACnetEventState
R
Always normal. Check status flags for real condition.
Out_Of_Service
BOOLEAN
R/W
Units
BACnetEngineeringUnits
R
Property Identifier
Property Datatype
Code
Remarks
Object_Identifier
BACnetObjectIdentifier
R
Object_Name
CharacterString
R
Object_Type
BACnetObjectType
R
Present_Value
REAL
W
Status_Flags
BACnetStatusFlags
R
Status flags will display the status of the channel fault =
false for normal conditions. Overridden = false if the
channel is not forced.
Event_State
BACnetEventState
R
Always normal. Check status flags for real condition.
Out_Of_Service
BOOLEAN
R/W
Units
BACnetEngineeringUnits
R
Priority Array
BACnetPriorityArray
R
Relinquish_Default
REAL
R
*